Maple Armor Fire Watcher 2841 - Conventional Zone Module
The FW2841 Conventional Zone Module is an intelligent, addressable device designed to operate with a Maple Armor fire alarm control panel(s). It requires one address on the signaling line circuit (SLC).
This module interfaces and monitors 2-wire conventional detectors in Class B wiring. The initiating zone can support a mix of 2-wire conventional automatic detectors and normally open dry contact alarm initiating devices such as mechanical heat detectors and manual stations.
Features
• Durable material and solid parts
• Visible status LED indicators for alarm and trouble
• Easy installation
• Supports Class A and Class B input circuits
• Mounts to a standard 4-inch square electrical box
• For dry indoor installation
• Up to 252 addressable devices per loop
• Address programmed via handheld programmer